== Technical Details == | == Technical Details == | ||
The roaster uses a Watlow PID controller (on the left) to control air temperature. It outputs a process value (4-20 mA), which an Avatar Instruments power controller uses to change the power to the heater via SCR phase dimming. The Avatar supports 240 V but the heater itself only can handle 208 V. This machine was designed to operate on 208 V but JavaMaster confirms it can operate on 240 V with an adjustment. Originally, JavaMaster suggested we limit the PID to 70% max output power. But that resulted in unexplained oscillations in temperature typically +/- 30 F. The Avatar includes an optional feature to limit output voltage via the V-LIM trim pot. This was adjusted so 100% on the PID corresponds to 208 V as measured by a true RMS voltmeter. | The roaster uses a Watlow PID controller (on the left) to control air temperature. It outputs a process value (4-20 mA), which an Avatar Instruments power controller uses to change the power to the heater via SCR phase dimming. The Avatar supports 240 V but the heater itself only can handle 208 V. This machine was designed to operate on 208 V but JavaMaster confirms it can operate on 240 V with an adjustment. Originally, JavaMaster suggested we limit the PID to 70% max output power. But that resulted in unexplained oscillations in temperature typically +/- 30 F. The Avatar includes an optional feature to limit output voltage via the V-LIM trim pot. This was adjusted so 100% on the PID corresponds to 208 V as measured by a true RMS voltmeter. If the machine is ever operated at 208 V again, it will require re-adjustment of this trim pot. | ||