Line 9: Line 9:
Back of the shop by the loading dock. Can't miss it.
Back of the shop by the loading dock. Can't miss it.


Lots of sketchy shit in this one.
Some sketchy shit in this one.


Single phase and 2 pole circuits wired to 3 phase breakers. One apparent circuit wired to 2 panels.
Single phase and 2 pole circuits wired to 3 phase breakers.


Several high amp 3 phase breakers that are unmapped.
Several high amp 3 phase breakers that are unmapped.
Line 21: Line 21:
! Breaker # !! Used !! What Is It
! Breaker # !! Used !! What Is It
|-
|-
| 14&16&18 || unused || 3 phase, 20 amp, 3 black. Wiring trough, boiler room. Possible dust collection circuit thru existing disconnect.
| 14&16&18 || unused || 3 phase, 20 amp, 3 black. Wiring trough, boiler room. Dust collection circuit thru existing disconnect.
|-
|-
| 19&16&18 || used || 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong.
| 19&16&18 || used || 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong.
|-
|-
| 22 || unused || this is a stray 208v single red wire on a 3 phase breaker that runs to a 3 phase disconnect in the boiler room. Should be disconnected and abandoned.(used to be paired with wires pp1-2 # 35&37)
| 22 || unused || this is a stray 208v single red wire on a 3 phase breaker that runs to wiring troughin the boiler room. Should be disconnected and abandoned.(used to be paired with wires pp1-2 # 35&37)
|-
|-
|}
|}
Line 47: Line 47:
|26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working.
|26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working.
|-
|-
| 35&37 || used || 40 amp 1 phase 240v thru a 3 phase disconect used as junction box to another 3 phase disconnect used as a 1 phase 35 amp disconnect. Compressor.
| 35&37 || used || Compressor 40 amp 1 phase 240v thru a 35 amp disconnect in boiler room.
|}
|}


Line 173: Line 173:
|-
|-
| 18 || yes. works. || Shop heating radiator fans and thermostats.
| 18 || yes. works. || Shop heating radiator fans and thermostats.
|-
| 20 || yes. works. || Outlet in closet
| 20 || yes. works. || Outlet in closet - By extension, WiFi
|-
|-
|}
|}