| Line 9: | Line 9: | ||
Back of the shop by the loading dock. Can't miss it. | Back of the shop by the loading dock. Can't miss it. | ||
Some sketchy shit in this one. | |||
Single phase and 2 pole circuits wired to 3 phase breakers | Single phase and 2 pole circuits wired to 3 phase breakers. | ||
Several high amp 3 phase breakers that are unmapped. | Several high amp 3 phase breakers that are unmapped. | ||
| Line 21: | Line 21: | ||
! Breaker # !! Used !! What Is It | ! Breaker # !! Used !! What Is It | ||
|- | |- | ||
| 14&16&18 || unused || 3 phase, 20 amp, 3 black. Wiring trough, boiler room. | | 14&16&18 || unused || 3 phase, 20 amp, 3 black. Wiring trough, boiler room. Dust collection circuit thru existing disconnect. | ||
|- | |- | ||
| 19&16&18 || used || 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong. | | 19&16&18 || used || 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong. | ||
|- | |- | ||
| 22 || unused || this is a stray 208v single red wire on a 3 phase breaker that runs to | | 22 || unused || this is a stray 208v single red wire on a 3 phase breaker that runs to wiring troughin the boiler room. Should be disconnected and abandoned.(used to be paired with wires pp1-2 # 35&37) | ||
|- | |- | ||
|} | |} | ||
| Line 47: | Line 47: | ||
|26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working. | |26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working. | ||
|- | |- | ||
| 35&37 || used || 40 amp 1 phase 240v thru a | | 35&37 || used || Compressor 40 amp 1 phase 240v thru a 35 amp disconnect in boiler room. | ||
|} | |} | ||
| Line 173: | Line 173: | ||
|- | |- | ||
| 18 || yes. works. || Shop heating radiator fans and thermostats. | | 18 || yes. works. || Shop heating radiator fans and thermostats. | ||
| 20 || yes. works. || Outlet in closet | |||
| 20 || yes. works. || Outlet in closet | |||
|- | |- | ||
|} | |} | ||