| 35&37 || used ||  Compressor 40 amp 1 phase 240v thru a 35 amp disconnect in boiler room.
| 35&37 || used ||  Compressor 40 amp 1 phase 240v thru a 35 amp disconnect in boiler room.
|}
<br />
The following is the result of wire tracing done 04/25/2017. Tucker
<br />
Conduits from this panel were sharpie labeled with letters for this mapping.
{|Class="wikitable sortable" border="1" style="td { border: 1px solid #000000}"
|-
! Conduit Label !! feed path !! What It Feeds
|-
| A || dead ends 20' into shop ||
|-
| B || into PB1-2, through wall into dock || 220V welder outlet on N wall above hydraulic pump
|-
| C || into PB1-2, then to Pj1-1, then down to PB1-1 || rear door exit sign, and sockets above PP1-1 labeled as PP1-1:10
|-
| D || conduit runs to PB1-2, but has no lines || no lines in this conduit
|-
| E || Junction in ceiling above cold metals, which feeds 3 things:
* hanging 220V 1phase twistlock above Johnson bandsaw
* fat pipe out of junction to south takes 90deg east and feeds hanging 120V sockets over lockers
*narrow conduit south takes 90deg turn and tracks back towards boiler room, feeding an unused junction/socket in the boiler room wall
**4th conduit from this junction goes north and dead ends
|-
| F || direct to lights in ceiling  ||Shop lights, 2nd row from the East wall
|-
| G || direct to lights in ceiling ||  shop lights, 3rd and 4th rows from East wall
|-
| H || across shop ceiling and down East wall || 120V outlet run along East wall of cold metals
|-
|}
|}